Two Stage, Gas fired Baltur Burners.
- Burner Series : BTG 20 LX
- Burner Operation : Two Stage
- Fuel Adaptability : Natural Gas ; LPG ; PNG
Technical Descriptions:
- Gas burner compliant with European standard EN676. Pneumatic operation at two progressive stages.
- Continuous modulation operation by installing P.I.D. controller in the control panel (to be ordered separately with modulation probe).
- Modulation ratio 1:3.
- Gas burner with low NOx and CO emissions in accordance with European standard EN676: class 3.
- Regulating combustion air and blast-pipe.
- Combustion air intake with throttle damper. Air flow adjustment with electric servomotor.
- Fully closing air damper on shutdown to avoid loss of heat through the chimney.
- Maintenance facilitated by the possibility of removing the combustion head without having to remove the burner from the boiler.
- Sliding boiler coupling flange to adapt the blast-pipe to the various types of boilers.
- Gas train CE version consisting of valve operation and safety pneumatically driven , minimum pressure switch , pressure regulator and gas filter
- Possibility to choose gas train with valve tightness control.
- Fail proof connectors for burner/gas train connection
- Gas train exit: high.
- Sound-proof plastic protective cover.
- Flame detection by ionisation electrode with connector for micro amp meter.
- 7-pole socket for burner electric and thermostatic supply.
- 4-pole socket for second stage control or for the connection of the PID electronic regulator.
- Electric protection rating: